Pima County Development Services
Building Safety & Sustainability Division
Gas Distribution Standards
These standards are taken from Chapter
12 of the Uniform Plumbing Code to help the homeowner to replace, modify
or reconnect a gas distribution system: For specific information refer
to the Plumbing Code or contact the Building Codes Division of Pima County
Development Services at 740-6490.
SIZING THE SYSTEM
- Gas systems are sized to ensure adequate gas
pressure and volume is provided at each appliance outlet. To determine
the size (diameter) of each section of pipe two things must be determined.
The demand in BTU'S, for each gas appliance, and the length (developed
length) of the piping from the gas meter to the appliance. See
Table 12-1 for the demands of typical gas appliances. All appliances
may be sized according to the listing plate attached to the unit.
- When
the demands and developed lengths have been determined Table 12-3
is used for Sizing Natural Gas systems. Liquefied Petroleum (LP)
systems use Table 12-7. There are several ways to use the tables.
One method provides that each branch length may be sized according
to the demand on that particular branch. Then, as each branch line
joins the main trunk, the demands are added until the meter is reached.
Another simple method uses the total developed length to size each
branch (this method is presented with the table 12-3 for easy use).
- Other systems such as CSST are sized in accordance with the manufacturers instructions that are based on ANSI standards.
TABLE 12-1
Minimum Demand of a Typical Gas Appliances (if no nameplate indicating demand)
|
|
| Domestic gas range |
65,000 |
| Barbecue |
50,000 |
| Water Heater 40 gal. |
50,000 |
| Domestic top burners |
40,000 |
| Domestic dryer |
35,000 |
| Water Heater 30 gal. |
30,000 |
| Fireplace log lighter |
25,000 |
| Domestic oven |
25,000 |
All other demands such as furnaces, boilers, etc., are
dependent upon the demand listed on the appliance. To determine demand
by cubic foot per hour (CFH) simply divide the BTU by 1,000. As an
example, a 85,000 BTU furnace requires 85 CFH.
INSTALLATION
- Metal gas piping shall not be bent. Changes
in direction shall be made by the use of fittings or combination of
fittings. Non-metallic pipe may bend to a radius not less than 20 times
the diameter of the pipe.
The depth the pipe must be buried is:
Metal pipe.........12 inches minimum
Plastic pipe........18 inches minimum
An 18 ga. copper tracer wire must
be installed with plastic pipe and must terminate above grade at both
ends. Plastic pipe must be factory labeled with the words "natural gas”.
Good
practice would support the pipe near joints to reduce strain
at the fitting.
Piping above grade must be supported as follows:
- ½” Every 6 feet
- ¾” Every 8 feet
- 1¼”+ Every 10 feet
- Gas piping installed on a roof shall be supported 1 1/2
inches above the roof on blocks or approved supports on intervals indicated
above.
- Gas piping installed underground shall be factory wrapped
(green coating). All joints shall be cleaned, coated with primer
and wrapped with two layers of approved plastic tape. Standard IS 13-91
describes these requirements.
- All exposed piping shall be
six inches above grade and properly supported.
- Unions shall
not be buried or concealed. An accessible shut off valve shall be installed
within three feet of each appliance in the same space with the appliance.
INSPECTIONS
- All excavations shall
be left open until the piping has been tested, inspected and approved.
- All gas piping must be tested to verify there are no leaks. The test
must maintain 10-psi minimum air pressure for at least 15 minutes with no loss of pressure. The installer is responsible to perform
the test and supply the testing equipment. The test must remain in place for the inspector to observe.
- The inspection of chimneys and vents on gas appliances shall be made after they are installed and before they are
covered or concealed.
- Combustion air must be provided for gas burning, appliances. Water heaters must be provided a F/T relief valve piped to the outside or an approved location.
- Reconnections require that the gas system be tested with a 10-psi air test as described in #2 above. Reconnection tests are required when the gas system has not been used for two months for industrial or commercial buildings, and 12 months for residential buildings.
TABLE 12-7 LP Gas
Liquefied Petroleum Gas piping systems are sized in the same
manner as natural gas. LP gas has more BTU,s per cubic foot than natural
gas so generally the piping will be smaller than natural gas piping. The
table below has the developed length along the top and the pipe sizes on
the left. The BTU outputs are arranged according to the length and pipe
site the same as table 12-3. Use the procedure as described for natural
gas but realize the columns are different.
Maximum Capacity of Pipe In Thousands
of BTU per Hour of Undiluted Liquefied Petroleum Gases
(Based on a Pressure Drop of 0.5 Inch Water Column)
Low Pressure 11” Water
Column
| |
| 275 |
189 |
152 |
129 |
114 |
103 |
96 |
89 |
83 |
78 |
69 |
63 |
55 |
| 567 |
393 |
315 |
267 |
237 |
217 |
196 |
185 |
173 |
162 |
146 |
132 |
112 |
| 1071 |
732 |
590 |
504 |
448 |
409 |
378 |
346 |
322 |
307 |
275 |
252 |
213 |
| 2205 |
1496 |
1212 |
1039 |
913 |
834 |
771 |
724 |
677 |
630 |
567 |
511 |
440 |
| 3307 |
2299 |
1858 |
1559 |
1417 |
1275 |
1181 |
1086 |
1023 |
976 |
866 |
787 |
675 |
| 6221 |
4331 |
3485 |
2992 |
2646 |
2394 |
2205 |
2047 |
1921 |
1811 |
1606 |
1496 |
1260 |